Eaton 9SX5K iRT3U/5KVA[4500W]
|
General |
ÅäÆ÷·ÎÁö |
On-line double conversion with PFC (Power Factor Correction) system |
±¸¼º |
Rack/Tower |
ÆÄÆ® ¹øÈ£ |
9SX5KiRT |
¿ë·® |
5000/4500 |
Å©±â H x W x D mm |
440 x 130 x 685 |
Áß·®(Kg) |
48 |
º¸Áõ |
3 years on electronics, 2 years on battery |
|
Electrical Input |
¿¬°á |
Hardwired - see manual for terminal block layout |
Input Voltage Range |
176-276V without derating (up to 100–276V with derating) |
°øĪ Àü¾Ð |
200/208/220/230/240V |
Frequency |
50/60 Hz autoselection |
Frequency Range |
40-70 Hz |
¼ô ½áÅ°Æ® Àü·ù |
90 A |
THDI |
<5% |
|
Electrical Output |
Àü¾Ð |
200/208/220/230/240V +/– 1% |
Àü¾ÐTHD |
< 2% |
Ãâ·Â Äܼ¾Æ® |
(8) IEC-320-C13
(2) IEC-320-C19
Hardwired - see manual for terminal block layout |
°úºÎÇÏ ³»·® |
102–110% : 120s, 110–125%: 60s, 125–150%: 10s, >150%: 500ms |
È¿À²(Á¤»ó ¸ðµå) |
Up to 94% in Online mode, 98% in Hi-Efficiency mode |
Ãâ·Â ÁÖÆļö |
50/60 Hz autoselect, frequency converter as standard |
ºÎÇÏ crest À² |
3:1 |
¹èÅ͸® °ü¸® |
ABM¢ç and Temperature compensated charging method (user selectable), automatic battery test, deep discharge protection, automatic recognition of external battery units. |
ÃàÀüÁö ½ÃÇè |
EBM (3U) |
Deep Discharge Protection |
Multilingual graphical LCD display |
|
Communications |
°¡Ã» °æº¸ |
1 USB port, 1 RS232 serial port (USB and RS232 ports cannot be used simultaneously), 4 dry contacts (DB9), 1 mini terminal block for remote On/Off and 1 for remote power Off, 1 DB15 for parallel operation. |
Relay Output |
1 slot for Network-MS card, ModBus-MS or Relay-MS cards |
|
Environmental & Standards |
¿ ¹ß»ê(BTU) |
<45dB |
°¡Ã» ¼ÒÀ½ |
0 to 40¡ÆC continuous |
Standards and Compliance |
IEC/EN 62040-1, UL 1778, CSA 22.2 |
Safety markings |
IEC/EN 62040 -2 , FCC Class A, IEC/EN 62040-3 (Performance) |
Ç°Áú |
CE, CB report (TUV), UL |
|
Physical |
Bundled With |
In the interests of continuous product improvement all specifications are subject to change without notice. | |